    Hi, i’m trying to model the dynamic response of a wind turbine-generator system but i don’t know how to couple the mechanical torque to the electromagnetic torque of pmsg generator, already modeled in the EMTP-RV. The mechanical torque was obtained from turbine model and basic mechanical power equations by using the control blocks of EMTP-RV. Also, i don’t know the correct way of initilization of variables. I’m not using the per unit values. I’m connecting a three-phase resisitive load at generator terminals. Can you help me?

    #6810
    anonymous
    Keymaster

    The mechanical torque is an input of the PMSM model. You can activate in the Control tab.

    Which variable are you looking to initialize? your control bloch or the machine? You have an history tab for the control block. For the machine, you may use the steady-state voltage field.