  • #6571
    anonymous
    Keymaster

    I am doing a TRV study on a 345 kV reactor breaker. I noticed the EMTP example splits the reactor model in two.  Why is this?

    Robert E Wilson

    #6573
    anonymous
    Keymaster

    Since the reactor’s capacitances are distributed in nature, the 2 levels are required to represent adequately the reactor behavior at high frequencies during current chopping,  which involves HF phenomena.

    EMTP-RV Tech Support Team